|
|
|
|
||
|
|
||||
|
|
Compact Sine Inverter Instructions for installation & use Applies to the following models: Output power: 700watt, 1000 watt, 1500watt, 2000
watt & 3000 watts
Output voltage: 110VAC and 230VAC output, 50Hz & 60Hz
Output frequency: 50Hz & 60Hz
Input voltage: 12VDC & 24VDC input
|
|
||
|
|
Table of Contents
Mounting holes & dimensions – 700watt to 1500watt Mounting holes & dimensions – 2kW & 3kW Setup – DIP switches for output frequency & power-save mode Status indicator lamps & protection thresholds High surge & high inrush loads |
|
||
|
|
3. Installation
Choosing a location
Choose a location where the unit will not be subjected to water spray, dust, or insect ingress. Locations subjected to high temperature or vibration must be avoided if performance and reliability are not to be impaired. The inverter may be mounted in any orientation, but ensure that there is sufficient clearance around the unit to allow air to circulate without undue restriction. Ideally, the unit should be located close to, but not immediately adjacent to, the battery. This is to minimise voltage drop in the DC input leads. Connections
INCORRECT CONNECTION MAY CAUSE DAMAGE PLEASE FOLLOW THESE INSTRUCTIONS CAREFULLY Before proceeding, ensure that the inverter front panel switch is in the Off position. EARTHING - The “chassis ground” terminal on the inverter rear panel must be wired to the vehicle chassis (or protective earth if used in a building). Minimum wire size is 6mm2 for length up to 1 metre, otherwise 16mm2. DC INPUT - Two DC input bolts are provided on the rear of the unit with the label & moulding colours showing polarity and nominal input voltage. The DC power cables must be connected in the following sequence:
Cables should be run directly from the inverter studs to the batteries, with a suitable fuse at, or near to the battery positive. In order to minimise feed voltage drop and prevent fire risk, it is essential to use cables capable of handling the high current drawn. If the voltage drop is excessive, the inverter low voltage cut-off may operate prematurely & surge capability will be impaired. The table below gives recommended minimum cable & fuse sizes for typical installations. Note the maximum cable length; longer cables may cause damage to the inverter. Performance will be improved by using larger or shorter cables wherever possible. A design tool on the http://www.antares.co.uk/technical (If you are viewing an electronic version of this document, click above to connect to the design tool) If you need power cables to be made up for your
installation, please contact Antares ( |
|
|
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
Minimum input cable size & recommended battery supply input fuse:
Note that these are minimum cable sizes; performance will be improved by using larger or shorter cables wherever possible.
Note: cable length is the total of each of the two cables connecting the inverter to the battery. Battery stud fuses are available from Antares ( REMOTE CONTROL – An RJ11 telephone style connector on the inverter rear panel provides for connection of the remote control module, or combined remote control & display panel, both of which are available as optional accessories. Part numbers are: Remote control & display panel, 12 volts: 91072 Remote control & display panel, 24 volts: 91073 Remote control module, 12 volt only: 70577, plus loaded software version part no. Note: The remote control module allows the inverter to be switched on & off remotely, using a 12 volt DC signal. The remote controller response is controlled by it’s own software, which can be programmed on request to meet the specific needs of the application. At the time of writing, standard variants are: i. Ignition controlled ii. Ignition controlled, with 10 minute run-on after ignition off. Please enquire if you would like more details on the options available. AC OUTPUT - The AC output available at the socket on the front panel may be routed to the point of use using normal mains cabling, extension leads or multiple outlet socket strips. You will need to decide on the need for a residual current detection device at the output, & whether to earth the inverter’s neutral or to leave it floating (as supplied). Guidance on the electrical safety of inverter
installations on vehicles is accessible on the http://www.antares.co.uk/technical (If you are viewing an electronic version of this document, click above to connect to the design tool) Alternatively, the document is available on request from
Antares (
Note: If you have purchased a 110VAC output inverter with |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
Mounting hole locations are shown below; 700 watt, 1000 watt
& 1500 watt models: |
|
|
|
|
|
|
|
|
|